Click on Image
Warranty : 2 Years
Warranty for Battery : 1 YearNo Retail Box Included
Capacity 2000 VA / 1800 W
Low Line Transfer 180VAC/160VAC/140VAC/120VAC±5%
Low Line Comeback 195VAC/175VAC/155VAC/135VAC ± 5 %
High Line Transfer 300 VAC ± 5 %
High Line Comeback 290 VAC ± 5 %
Frequency Range 40Hz ~ 70 Hz
Phase Single phase with ground
Power Factor 0.99 @ nominal voltage (input voltage)
Output Voltage 208/220/230/240VAC
Output Power Factor 0.9
AC Voltage Regulation ±1% (Battery Mode)
Frequency Range 47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
Frequency Range (Battery Mode) 50 Hz ± 0.5% or 60Hz ±0.5%
Overload 105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal
110%~130%: UPS shuts down after 1 minute at battery mode or transfer to bypass when the utility is normal
130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal
Current Crest Ratio 03:01
Harmonic Distortion 3 % THD (linear load); 6 % THD (non-linear load)
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform (Battery Mode) Pure Sinewave
AC Mode 89%
Battery Mode 87%
Battery Type 12 V / 9 AH
Battery Numbers 4
Recharge Time 4 hours recover to 90% capacity (Typical)
Charging Current 1.0 A (max.)
Charging Voltage 54.7 VDC ± 1%
Dimension, D × W × H, mm 397 × 145 × 220
Net Weight (kgs) 17
Operation Humidity 20–90% RH @ 0–40°C (non-condensing)
Noise Leve Less than 45dBA @ 1 Meter